CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
120
Replacing the BACNET-GW The BACnet Feature
13.Click SAVE.
8.11 Replacing the BACNET-GW
The CGW-MB and the BACNET-GW-3 have different addressing schemes. Refer to the
Compatible Equipment section for the supported objects details.
Ensure that the replacing CGW-MB has correct object addresses and the old object
mappings of BACNET-GW-3 are removed.
Refer to the BACnet PIC Statement section for the CGW-MB object addressing details.
1. Ensure that the BACnet feature in the CGW-MB is licensed.
2. Go to CGW-MB Web Configuration Tool.
3. Click the BACnet Settings tab.
4. Ensure that the below BACnet settings are same in the CGW-MB:
Static IP address
BACnet Port Number
Foreign device configurations
Node mapping
Network Number
5. Delete the replaced BACnet CLSS Gateway mainboard related objects on the BACnet
client.
6. Connect the CGW-MB.
7. Rediscover the BACnet objects.
Or
Restart the BACnet client.
8. Modify the client graphics according to the rediscovered objects.
8.12 Using Both the CGW-MB and the Legacy BACnet CLSS Gateway
mainboard
The CGW-MB and the BACNET-GW-3 have different addressing schemes. Ensure that
they are assigned with their own addressing scheme.
Refer to the BACnet PIC Statement section for the CGW-MB object addressing details.
1. Ensure that the BACnet feature in the CGW-MB is licensed.
2. Go to CGW-MB Web Configuration Tool.
3. Click the BACnet Settings tab.
4. Configure the BACnet settings in the new CGW-MB.
Refer to the To Configure the BACnet Settings section for the configuring procedure.
5. Connect the CGW-MB and rediscover the BACnet objects.
6. Modify the client graphics according to the new instance numbers (object addresses).
Fields Action
Equipment Supervision
and Monitoring
Click to set Priorities of Events
General Alarm Click to set Priorities of Events
Fire Supervision Click to set Priorities of Events
Process Trouble Click to set Priorities of Events
System Status Active Click to set Priorities of Events
Set to default Click to set the priorities to default