CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022 55
CGW-MB Control Features Modbus Communications
Zone Commands
7.19.4 Sending Commands
Send commands through the CGW-MB by writing command values to the appropriate
holding registers. For detailed register mapping information refer to the
7.21 "Register
Mapping"
section. The following tables display the values representing all the command
types for nodes, points, and zones.
For Panels of All Brands
Table 7.8: Node Commands
Serial
No
Command value Holding Register
1 ActivateDeactivateSounder 0x1300 - Activate
Use Zone Holding Register
number
2 ActivateDeactivateSounder 0x1400 - Deactivate
Use Zone Holding Register
number
3 EnableDisableZone 0x0600 - Enable
Use Zone Holding Register
number
4 EnableDisableZone 0x0700 - Disable
Use Zone Holding Register
number
3 SetZoneMode 0x1500
Use Zone Holding Register
number
4 TerminateTest 0x12
Use Zone Holding Register
number
Table 7.7: Zone Command Availability by Panel
General Zones Logic Zones
Trouble/Release
Zones
Panel Type
Enable/
Disable
Activate/
Deactivate
Enable/
Disable
Activate/
Deactivate
Enable/
Disable
Activate/
Deactivate
AFP-2800
Yes No No No No No
AFP-3030
Yes No No No No No
N16
Yes Yes Yes No No No
NFS-320
Yes No No No No No
NFS-640
Yes No No No No No
NFS2-640
Yes No No No No No
NFS-3030
Yes No No No No No
NFS2-3030
Yes Yes Yes No No No
XLS 120
Yes No No No No No
XLS 140-2
Yes No No No No No
XLS 2000
Yes No No No No No
XLS 3000
Yes Yes Yes No No No
Command Value Holding Register
Reset 0x0000 20001
Silence 0x0001 20001