CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
118
To Connect with the BACnet Client The BACnet Feature
11.Find and click BACnet Settings in the CLSS Gateway mainboard Settings section.
12.Specify the required values as in the below table:
Fields Action
Enable BACnet
functionality
Select to enable the BACnet application.
Notification Type Select Life Safety or Multi-state suitable to the customer
requirement.
Network Number Specify a network number of this BACnet CLSS Gateway
mainboard. It helps to identify the CLSS Gateway mainboard
when multiple CLSS Gateway mainboards are in the network.
Note: Sometimes two or more CLSS Gateway mainboards in
the same network might use the BACnet feature. Each of
them should have its own unique network number. Ensure
that the difference between any two network numbers is at
least 100.
BACnet Port Specify the BACnet port.
The universal default port number is 47808.
Its range can be: 47808 - 47823 (0xBAC0 - 0xBACF)
Object Addressing Select the addressing type. Options: IFOM Addressing or
Flexible Addressing.
Note: Flexible addressing is available only for Gent panels.
FOREIGN DEVICE CONFIGURATION
Foreign Device Select to enable the foreign device.
IP Address Enter the BBMD Server IP address.
Port Enter the BBMD Port number.
Register Time Specify the time in seconds. As per this value, the device will
periodically re-register with the BBMD to maintain full
participation in the BACnet/IP network.
Note: Maximum value is 30 seconds.