CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
124
BACnet PIC Statement The BACnet Feature
Standard Object Types Supported - Multi-State Input /Multi-State Output / Multi-State Value
Status Flags
Boolean
BACnet Status
Flags Fire Panel State
0,0,0,0 Normal Normal
1,0,0,0 InAlarm Fire Alarm, Security Alarm
(Life/Property), Critical Process Alarm
(Life/Property), Medical Emergency,
PreAlarm, IB Smash Glass, Panic
Alarm
0,1,0,0 Fault Security Trouble, Fire Trouble, Non-
Fire Trouble
0,0,0,1 OutOfService Fire Device or Zone Disabled, Non-
Fire Device Disabled
1,0,0,1 InAlarm,
OutOfService
If device is in Alarm state (Fire Alarm,
Security Alarm (Life/Property), Critical
Process Alarm (Life/Property),
Medical Emergency, PreAlarm, IB
Smash Glass, Panic Alarm) and also
device goes to disable state(Fire
Device or Zone Disabled, Non-Fire
Device Disabled)
0,1,0,1 Fault,
OutOfService
If device is in trouble state (Security
Trouble, Fire Trouble, Non-Fire
Trouble )and also device goes to
disable state(Fire Device or Zone
Disabled, Non-Fire Device Disabled)
Out of Service
Boolean Fire Panel State
0 FALSE All statuses other than disable
1 TRUE Fire Device or Zone Disabled, Non-
Fire Device Disabled
Present Value
BACnet
Enumeration
Fire Panel State
1 None Normal
2 None All statuses other than those
included in 3 and 4 below.
3 None Security Trouble, Fire Trouble, Non-
Fire Trouble
4 None Fire Device or Zone Disabled, Non-
Fire Device Disabled