Getting Started
Part No.: 4417584_Rev12 Configuration Manual
CIU 888 3 - 68
8. Click the Temperature tab, the Properties detail appears.
You can view or edit these properties:
Water dip enabled Check to enable water level scan from servo gauge.
Water dip offset Enter water level offset.
Minimum water level Enter minimum water level. This value is used when
no water level is found.
Water address Enter water level transmission address.
Water TOI Select B, C, E, or M*.
Water TOR Select M, J, B, L or ZLQ
Water in foreground scan Check to enable the option.
* Refer to TABLE 3-1 for additional information.
Properties Description
Temperature enabled Check to enable product temperature scan.
Element type Select No element available, MRT, MRT with bottom
spot, MRT with bottom and top spot, One spot
element, Two spot element or MTT.
Lowest element
Position
Enter lowest temperature element position.
Temperature address Enter product temperature transmission address.
Temperature TOI Select: B, C, E, or M*.
Temperature TOR Select: C or ZAG*.
Temperature in fore-
ground scan
Check to enable the option.
Temperature profile scan
enable
This parameter enables / disables the temperature pro-
files data collection from a BPM gauge by CIU.
When this option is selected, CIU collects temperature
profiles data from the BPM gauge that is configured for
product temperature.
Note: CIU would collect the temperature profile data
from the gauge from which product temperature is
scanned.
Properties Description