100 IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
System Operation Basic Operation
9.3.8 Manual AlarmNet Registration
1. From the main menu, press 1 for System Tests.
2. Select 8 to access Register AlarmNet. The screen will display and ask for confirmation. Feedback will be given if the command was
sent or not.
9.3.9 Silence Alarms or Troubles
1. When an alarm is sounding, press SILENCE and enter your code or rotate the key at the prompt.
If an external silence switch was installed, activating the switch will silence alarms or troubles.
If you are actively using the system menus when you press SILENCE, you do not need to enter your code or rotate the key.
9.3.10 Reset Alarms
Press RESET and enter your code or rotate the key at the prompt. If an external reset switch was installed, activating the switch will reset the
alarms.
Reset Communicator
This options allows the user to reset the communicator. The LCD will display, “Communicator Reset in progress… Please Wait”. You will be
returned to the main menu when the reset is complete.
The communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the follow-
ing events are active:
•Fire Alarm
Fire Supervisory
Fire Pre-Alarm
CO Alarm
CO Supervisory
9.3.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72.
If the sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a
CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the Central Station receives a detector trouble report (“373” and the zone or point for Contact ID for-
mat; “FT” and the zone or point in SIA format). To check the sensitivity for an individual detector, follow the steps below:
1. From the main menu, press 2 to access Point Functions.
2. Press 2 to access Point Status.
3. Select the desired module.
4. Enter the number of the desired point and press ENTER.
5. A screen similar to those shown below will display.
NOTE: Alarm and trouble signals that were silenced will resound every 4 or 24 hours, depending on user programming, until the trouble is
cleared.
NOTE: This system has the ability to silence control panels across the ECS network.
NOTE: Multi-Site displays do not reset multiple sites. To reset a site, enter a Multi-Site Installer access password, select a site from the list of
Sites, and then press Silence or Reset button to continue. This option will occur whether the Network was programmed No/Yes for “Silence-
Reset Across Sites”. Also, this option allows the user to select Reset Fire System and Reset Emergency Communication System whether or not
the panel has ECS. If the user selects No, the non-ECS panel will do a fire reset within the site and no other sites will be affected.