88 IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Programming System Options
5. Enter the Point Number, then press ENTER.
6. Press the up or down arrows to select the type (Notification or unused). Press ENTER.
7. Press the up or down arrows to select the desired Group, then press ENTER.
8. Edit the module name. (See Section 8.5.) Or, press the right arrow to skip the module name edit.
9. Repeat steps 1 through 8 for all points.
To program 5880 or 5865 module input points:
10. To use the 5880 as an input point, Enter point number 41 - 48. Then press ENTER.
11. Press the up or down arrow key to select type (switch or unused), and press ENTER.
12. Press the up or down arrow key to select the desired function and press ENTER.
13. If the point supports latching press the up or down arrow key to select latching or non-latching, and press ENTER.
14. Press the up or down arrow key to select the desired group/zone, and press ENTER.
15. Edit the point name or press the right arrow key to skip the Module Name Edit.
16. Repeat steps 10 through 15 for all input points.
8.5.4 Point Programming for the 5496
To program the module points:
1. Login to the panel. The panel will automatically access the Main Menu.
2. Select 7 for Panel Programming.
3. Press 4 to enter point menu.
4. Press the up or down arrow key to select the desired module. Refer to Section 8.5.4 for available choices, then press ENTER.
5. Enter the point number, then press ENTER.
6. Press the up or down arrow key to select the type and press ENTER.
7. Press ENTER to edit the Point Name. See Appendix A for help with editing names or press the right arrow key to skip the Point Name
Edit.
8. Repeat Steps 1 through 7 for all points.
8.6 System Options
This section of the manual explains how to customize software options that affect general operation of the system.This includes:
• Communication Options
• Daytime/Nighttime Sensitivity
• Holiday Schedule
• Telephone and Reporting Account options
Refer to each individual subsection for the complete instructions.
8.6.1 Communication Options
Auto Test Time
To access the Auto Test Time screen:
1. Login to the panel.
2. Select 7 to access the Program Menu.
3. Select 5 to access System Options.
4. From the next Menu, select 1 to access Communication Options.
5. Select 1 to access Auto Test Time.
6. Enter the hour you want the control panel to send an Automatic Test Report (or press the up or down arrow key), then press ENTER.
7. Enter the minutes (or press the up or down arrow key), then press ENTER.
8. Select AM or PM by pressing the up or down arrow key, then press ENTER.
M01 P001 NOTIF
G01
MODULE_1 CKT_1
<Enter Pt or <=Exit>
Select NOTIF or UNUSED.
Select an output group for this notification point.
Select the circuit to program.
Select a name for the point.
Figure 8.6 Programming Output Points Screen for 5880 and 5865 Modules
M01 P048 SWITCH
Z001
MODULE_1 CKT_1
<Enter Pt or <=Exit>
Select SWITCH or UNUSED.
Select an input zone.
Select the point to program.
Select a name for the point.
Figure 8.7 Programming Input Points Screen for 5880 or 5865 Modules