14 IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Agency Listings, Approvals, and Requirements Underwriters Laboratories (UL)
2.2.6 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station with emergency response, both aspects meet-
ing the Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.
2.2.7 NFPA Requirements
The following is the minimum configuration necessary to comply with the NFPA requirements.
Model/Module Description Local Releasing
Remote
Station
Auxiliary
C e n t ra l
Station
Emergency
Signaling
IFP-75 Control Unit Y Y Y Y Y Y
5220 Direct Connect Module N N N Y N O
5496 NAC Expander O Y* O O O O
5865-3/-4 LED Annunciator O O O O O O
5880 LED I/O Module O O O O O O
RPS-1000 Intelligent Power Module O Y* O O O O
RA-100 LCD Annunciator O O O O O O
RA-1000 LCD Annunciator O O O O O O
RA-2000 LCD Annunciator O O O O O O
SK-NIC Network card O O O O O O
SK-FML/ -FSL Fiber modules O O O O O O
IFP-75CB or IFP-75BCB Enclosure Y Y Y Y Y Y
CELL-MOD/CELL-CAB-SK Cellular transmitter O O O O O O
HWF2A-COM Communicator N N Y N Y N
HWF2V-COM Communicator N N Y N Y N
Y = YES, N = NO, O = OPTIONAL
Note: Y * = You must include the RPS-1000 or 5496 for releasing purposes.
Table 2.1 NFPA Requirement for Minimum System Configuration for IFP-75