IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022 87
Point Programming
8.5.3 Point Programming for 5880 and 5865 Modules
To program for the 5880 or 5865 module points, follow these steps:
1. Login to the panel.
2. Select 7 to access the Program Menu.
3. Press 4 to enter the Point Menu.
4. Press the up or down arrows to select the desired module. Refer to Section 7.5 for available choices. Press ENTER.
Choices Type Selections
Function Selections
for each Type
Comments
Enter Point or Circuit
Select Type UNUSED
NOTIF OUT
CTRL CKT
AUX PWR CONSTANT Constant auxiliary power.
RESETTABLE Resettable auxiliary power.
DOOR Door holder auxiliary power.
AUX SYNC Sounder Sync auxiliary power for System Sensor
B SWITCH* MAN PULL Refer to comments column of Table 8.4 for description of these options
Latch or Non-latching feature only appears for waterflow, supervisory,
tamper, zone aux1, zone aux2, system aux1, and system aux2
WATERFLOW
SUPERVSY
TAMPER
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
STATUS POINT Non-latching - Used to activate an ancillary output group that does not
active alarm, sound PZT, display status or report events. Reset has no
affect on this point
A SWITCH* Same as B SWITCH
B DETECTOR* 2-WIRE SMOKE Used for Class B, 2-wire detectors.
4-WIRE SMOKE Used for Class B, 4-wire detectors.
CO 4-WIRE DET Used for Class B, 4-wire CO detectors.
CO 4-WIRE SUP DET Latching or Non-latching used for Class B, 4-wire CO Supervisory
detectors
A DETECTOR* 2-WIRE SMOKE Used for Class A, 2-wire detectors.
4-WIRE SMOKE Used for Class A, 4-wire detectors.
CO 4-WIRE DET Used for Class A, 4-wire CO detectors.
CO 4-WIRE SUP DET Latching or Non-latching used for Class A, 4-wire CO Supervisory
detectors
Select Group Group or Zone selection will appear depending on the type selected
Edit Name Edit name. See Section 8.5.3
*Only applicable to the RPS-1000
Table 8.5 Menu choices for Internal/External Power Modules