Model IFP-75/IFP-75HV Basic Operating Instructions
These instructions must be framed and displayed next to the IFP-75
panel in accordance with NFPA 72 fire code for Local Protected Fire
Alarm Systems. Test the system in accordance to NFPA 72.
Operation Task to Perform
Silence Alarms and Troubles
Press SILENCE and then enter a code if prompted. The Silence LED will light.
Reset Alarms
Press RESET and then enter a code if prompted.
View Alarms, Supervisories,
and Troubles
Press up or down arrow to view Alarms, Supervisories, or Troubles.
View a Points Status
1. Login to the panel.
2. Press 2 to select Point Functions.
3. Press 2 to select Point Status.
4. Select the desired module by using the up or down arrows. Then press ENTER.
5. Enter the point number.
Conduct a Fire Drill
1. Login to the panel.
2. Press 1 to select System Tests.
3. Press 1 to select Fire Drill.
4. Press ENTER to start the fire drill. Press ENTER to end the fire drill.
Check Detector Sensitivity
1. Login to the panel.
2. Press 2 for Point Status.
3. From the list that displays, select the SLC module where the desired point is located.
4. The fourth line of the display shows the sensitivity status.
“NORMAL” means the detector is in compliance with NFPA 72.
“CAL MAINT” means the detector is in compliance with NFPA 72 but maintenance should
be performed soon.
“CAL TRBLE” means the detector is not in compliance with NFPA 72.
Set Time and Date
1. Login to the panel.
2. Press 4 to select Set Time & Date.
3. Make changes in the fields on the screen as necessary.
4. When the time and date are correct, press ENTER.
Enable / Disable a Point
1. Rotate the key or enter a code to access to access Main Menu.
2. Press 2 to select Point Functions.
3. Press 1 to select Disable / Enable Point.
4. Press 7 to select Disable / Enable Point.
5. Use the up or down arrow to move through the list. Then press ENTER to select the
module where the desired point is located.
6. Enter the point or circuit number that you want to disable/enable.
7. Press the right arrow key to toggle between NORMAL (enable) or DISABLE.
View Event History
1. Login to the panel.
2. Press 3 to select Event History.
3. Press the up or down arrow to view events in the history buffer.
For Service Call:
P/N LS10165-001SK-E Rev C ECN: 151770
FIRE: ALRM SUPR TRBL
CO: ALRM SUPR
SYS: TRBL
FIRE: ALARM
Waterflow Sw
Zone_1
1 of 1 Info>