EasyManua.ls Logo

Honeywell Farenhyt IFP-75HV - 2: RA-2000 Connection to the Panel; 5824 Serial;Parallel Printer Interface Module Installation; 1: Selecting 5824 Options

Honeywell Farenhyt IFP-75HV
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42 IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Control Panel Installation 5824 Serial/Parallel Printer Interface Module Installation
4.9.2 RA-2000 Connection to the Panel
Connect the RA-2000 to the panel as shown below.
4.10 5824 Serial/Parallel Printer Interface Module Installation
The 5824 Serial/Parallel Printer Interface Module allows you to connect a printer to the panel. Printing is available for real time events,
detector status and event history.
5824 installation involves the following steps.
1. Ensure the power is off at the panel.
2. Connect the 5824 to the panel as shown in Figure 4.28.
3. Use the DIP switches on the back of the board to assign an ID# to the 5824 (see Section 4.13.1).
4. Configure the 5824 device through programming. See Section 4.10.1.
5. Connect a printer to the 5824 as shown in Figure 4.28.
4.10.1 Selecting 5824 Options
Configuring the 5824 includes the following steps:
Add the module to the system. JumpStart will add the module automatically (see Section 8.2). You can also add it manually (see
Section 8.2.2).
Select a name, if desired.
Select options for the printer and the output port. See below.
Printer and Output Port Options
1. From the Main Menu, select 7 for Program Menu.
2. Select 1 for Module.
3. Select 1 for Edit Module.
4. From the list that displays, select the desired 5824 module.
SB
SA
S+
S-
NO NC C
TROUBLE
SLC IN
+
_
SLC OUT SLC PROG
+
_
+
_
SBUS
A
B
+
_
NAC 1
NAC 2
supervised,
power-limited,
Class B
Figure 4.27 RA-2000 Connection to the Panel
NOTE: There is a maximum of four 5824 modules per panel.
NO NC C
TROUBLE
SLC IN
+
_
SLC OUT SLC PROG
+
_
+
_
SBUS
A
B
+
_
NAC 1
NAC 2
S
+
S
-
ON
12345
A
B
S
B
U
S
DIP switches
5824
connectors for
connection to
printer
parallel
serial
supervised,
power-limited,
Class B
FACP
Figure 4.28 5824 Connection to the Panel

Table of Contents