IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022 57
SK-NIC Installation Networking
2. Use the 6-pin cable included with SK-NIC to connect the IFP-75 to the SK-NIC. The 6-pin cable must be run in conduit between
cabinets. Refer to Figure 5.1.
3. Each SK-NIC has the ability to monitor for earth ground faults on the twisted-pairs connected to Port 1 of its terminal block TB2. Earth
fault detection for any wiring at Port 2 of TB2 is done at the next/previous SK-NIC due to these wiring connections being connected to
Port 1 of TB2 at the next/previous SK-NIC.
4. Unused optic ports on fiber loop modules must have their dust caps placed on the port.
5. Based on the type of data medium chosen, run the twisted pair wiring/fiber-optic cable to the next SK-NIC using a Class B or Class X
wiring method. A combination of both medium types can be used. See Figure 5.6 through Figure 5.9 for SK-NIC wiring examples.
5.4.1 Wiring
Unshielded Twisted Pair Wiring between Multiple Panels
Unshielded twisted-pair wiring between multiple panels is shown in Figure 5.6. Class X wiring is shown with a dotted line.
LED1
LED2
RX
TX
Figure 5.5 Panel to SK-NIC Connection
A
B
A
B
A
B
A
B
A
B
A
B
TB2
TB2
TB2
last control panel/SK-NIC
next control panel/SK-NIC
first control panel/SK-NIC
port 2
port 1
port 2
port 1
port 2
port 1
Figure 5.6 Twisted Pair Wiring Configuration
Class X
wiring