118 IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Reporting SIA / IFP-75 Panels PI Modifier Reporting
10.2 SIA / IFP-75 Panels PI Modifier Reporting
Events are sent to the Central Station as a variable length string:
The Event Format is:
EEZZZZ
Where the Event Format is defined as follows:
• The account number is sent using an account block that is separate from the event block.
• Multiple events can be sent within a single event block. Events are separated by a “/” character.
• The event parameter can be a zone, point or module number.
• When reporting-by-point is enabled, the communicator uses a “pi” event to supersede the actual point event to report the module to
which the point is linked.
• The panel ID is not sent in the SIA event parameters.
See Table 10.3 below for an example.
Code Event Code Description
EE
Event Code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
Event
Report
Zone/Point
Panel
ID
Module
Zone
ZZZZ
Point ZZZZ Fields Sent SIA Event Data
Fire Alarm-Zone Zone n/a n/a 15 n/a EE-ZZ FA15
Fire Alarm-Zone Zone n/a n/a 05 n/a EE-Z FA5
Fire Alarm-Point Point n/a 01 n/a 123 EE-ZZ /EE-ZZZ pi01/FA123
Fire Alarm-Point Point n/a 33 n/a 203 EE-ZZ/EE-ZZZ pi11/FA203
Expander Trouble n/a n/a 11 n/a n/a EE-ZZ ET11
Auto Test n/a n/a n/a n/a n/a EE-Z RP0
Battery Trouble-Panel 32 n/a n/a 98 n/a n/a EE-ZZ YT98
Battery Trouble-Expander 18 n/a n/a 18 n/a n/a EE-ZZ YT18
SLC Loop Shorted n/a n/a 44 n/a n/a EE-ZZ ET44
Program Begin Panel ID=32 n/a n/a n/a n/a n/a EE-Z LB0
Program Begin Panel ID= 22 n/a n/a n/a n/a n/a EE-Z LB0
AC Power Loss - Panel 22 n/a n/a 98 n/a n/a EE-Z AT0
Fire Trouble Point n/a 97 n/a 200 EE-ZZ /EE-ZZZ pi97/FT200
Fire Trouble Zone n/a 97 01 n/a EE-Z FT1
Fire Trouble-NAC Point n/a 98 n/a NAC Circuit 2 EE-ZZ /EE-Z pi98/FT2Z=Pt. #
Fire Trouble-NAC Zone n/a 98 n/a NAC Circuit 2 EE-ZZZ FT98 ZZZ=OP
Table 10.3 SIA- IFP-75 Panels - PI Modifier Reporting Examples