IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022 29
AC Power Connection Control Panel Installation
4.4 AC Power Connection
At installation, connect the AC terminals to the power source as shown in Figure 4.5. It may be necessary for a professional electrician to
make this connection.
• AC power for the IFP-75 is rated at 120VAC, 60Hz, 1.5A.
• AC power for the IFP-75HV is rated at 240VAC, 50/60Hz, 1A.
Note: 0.25” spacing must be
maintained between each of these
circuit types; as well as between
power-limited and non-power-limited
circuits.
Figure 4.4 Wire Routing Example
NAC circuits
SBUS
SLC
Phone lines
Relays
Battery
connection
Battery Battery
AC input
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF
POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR
INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED