62 IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Network Management Sync Network Options
The selections for this option are as follows:
pi modifier (default)
•Panel ID*
Receiver Configuration
The IFP-75Network can report events to as many as 68 receivers. See Appendix B for a list of the panel/receiver relationship numbers. Each
receiver can be assigned the reporting credentials. When you use a format that supports phone numbers, the format can be up to 40 digits
long.
1. From the Main Menu, do the following.
2. Select 6 to access the Network Programming.
3. Press 6 to enter Communicator Options Menu.
4. Select 3 to access the Receiver Configuration.
5. Select the panel to program and press ENTER.
6. Enter the receiver number to which you want to report. The receiver numbers available will correspond with the panel number you
entered. The receiver numbers are populated based on the panel number and audited to allow only the four appropriate receivers. See
Appendix B for a list of receiver numbers.
The available format choices are:
Contact ID
SIA500
•SIA8
•SIA20
Ethernet
Cellular
UNUSED
Communicator Reporting Table
The Communicator Report Table specifies the Event Reporting for each panel on the network. Each row in the table specifies the following.
Also, associated with the receivers are the account number and the daily test option. The table format can have up to 99 rows.
1. From the Main Menu, select 6 to access the Network Programming.
2. Press 6 to enter the Communicator Options Menu.
3. Select 4 to access the Communicator Reporting Table.
4. Press * to add rows, Press ENTER to edit the data.
6.3 Sync Network Options
After you make changes to network programming, if the distribution of network options fail, the System will report a trouble of network
options out of sync. Use this Menu to redistribute the changed options to the rest of the network. The user will be required to choose a panel
from which to source the options. Scroll down through the informational message and press ENTER to view the Select Source screen.
1. Login to the panel.
2. Select 6 to access the Network Programming Menu.
3. Select 8 to access the Sync Network Options.
NOTE: *Only the SIA sends the Panel ID when reporting.
test primary account
test secondary account
Panel: 03 YYYY
R009:321456 N
R013:987456 N
<Help Text>
P#ASTP Prit Sect
01=03YYYY 009N 013N
02=02NNYN 015N 014Y
* = Add Row
panel number
primary receiver number
secondary receiver number
panel number
report alarms
report supervisories
report event by point (Y=point, N=zone)
report troubles
Figure 6.1 Communicator Reporting