IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022 17
Calculating Current Draw and Standby Battery Prerequisites for Installation
IDP-PHOTO-W/-IV
Standby: 0.2 mA
Alarm: 4.5 mA
2
mA mA
IDP-PHOTO-T-W/-IV mA mA
IDP-PHOTO-R-W/-IV mA mA
IDP-HEAT-W/-IV mA mA
IDP-HEAT-HT-W/-IV mA mA
IDP-HEAT-ROR-W/-IV mA mA
IDP-PHOTO-CO-W mA mA
IDP-CO-W mA mA
IDP-BEAM (without integral test) SLC Standby/Alarm: 2 mA mA mA
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
IDP-BEAM-T
3
(with integral test) SLC Standby/Alarm: 2 mA mA mA
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
OSI-RI-FH
SLC Standby/Alarm: 20 mA mA mA
Aux. Pwr Standby: 22 mA mA
Alarm: 20 mA mA
DNR/DNRW
4
(non-relay) None, included with IDP-PHOTO-R/-W/-IV
DNR
4
(with relay) None, included with IDP-PHOTO-R/-W/-IV & IDP-RELAY
IDP-FIRE-CO SLC Standby: 0.30 mA mA
Alarm: 7 mA mA
IDP-FIRE-CO-W/-IV SLC Standby: 0.20 mA mA
Alarm: 4.5 mA mA
IDP-PTIR-W/-IV SLC Standby: 0.20 mA mA
Alarm: 4.5 mA mA
Addressable SLC Modules
IDP-MONITOR Standby/Alarm 0.375 mA mA mA
IDP-MINIMON Standby/Alarm 0.375 mA mA mA
IDP-PULL-SA/IDP-PULL-DA Standby/Alarm 0.3 mA mA mA
IDP-MONITOR-2 Standby/Alarm: 0.75 mA mA mA
IDP-MONITOR-10 Standby/Alarm: 3.5 mA mA mA
IDP-CONTROL SLC Standby 0.375 mA mA
Alarm: 0.375 mA mA
Aux Pwr Standby 1.7 mA mA
Alarm: 6.5mA mA
IDP-CONTROL-6 SLC Standby 2.65 mA mA
Alarm: 35 mA mA
Aux Pwr Standby 8 mA mA
Alarm: 20 mA mA
IDP-RELAY Standby/Alarm: 0.255 mA mA mA
IDP-RELAY-6 Standby: 1.9 mA mA
Alarm: 32 mA mA
IDP-RELAYMON-2 Standby: 1.3 mA mA
Alarm: 24 mA mA
IDP-ZONE Aux Pwr Standby 12 mA mA
Alarm: 90 mA mA
SLC Standby: 0.27 mA mA
Alarm: 5.1 mA
Device # of Devices Current per Device
Standby
Current
Alarm Current
Table 3.2 Current Draw Worksheet for IDP SLC Devices (Continued)