24 IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Prerequisites for Installation Calculating Current Draw and Standby Battery
5865-3 LED Annunciator Module Standby: 35 mA mA
Alarm: 145 mA mA
5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface Standby: 0 mA mA
Alarm: (22 mA/relay) 220 mA mA
Network Cards
SK-NIC Network Interface Card Standby/Alarm: 21 mA mA mA
SK-FML Fiber Optic Multi Mode Standby/Alarm: 53 mA mA mA
SK-FSL Fiber Optic Single Mode Standby/Alarm: 79 mA mA mA
Wireless Modules
WIDP-WGI Wireless Gateway Max current using ext supply 40 mA mA mA
Max current SLC Power 24 mA mA mA
A Total System Current
Auxiliary Devices
5
Refer to devices manual for current rating
IPDACT-2 IP Communicator Standby: 93 mA mA
Alarm: 136 mA mA
IPDACT-2UD IP Communicator Standby: 98 mA mA
Alarm: 155 mA mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA mA
Alarm: 100 mA mA
HWF2-COM Series Standby: 210 mA mA
Alarm: 290 mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Notification Devices Refer to device manual for current rating
5495/5499 Power Supply Standby: 75 mA
mA
Alarm: 205 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C Notification Appliances Current
mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x 0.001): A A
F Number of standby hours H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes = 0.0833 hours) H
I Multiply lines E and H. Total alarm AH
AH
J Add lines G and I. AH
Multiply by the Derating Factor 1.25
Total ampere hours required
6
AH
1 The FACP can only support 5 devices with LEDs on. The current draw has been added to the panels alarm current.
2 Total does not include isolator devices or accessory bases
3 If using 24 VDC aux power only. No standby or alarm current is needed for battery calculation if using 24 VAC, 120 VAC, or 240 VAC.
4 Maximum SBUS address capacity is determined by the amount of SBUS bandwidth consumed by each SBUS module. Refer to
Section 4.6.2 for SBUS limitations.
5 If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that
time. However, during normal operation, door holders draw current and must be included in the 1.0A total current that can be drawn from
the panel.
6 Use next size battery with capacity greater than required.
Device # of Devices Current per Device
Standby
Current
Alarm Current
Table 3.4 Current Calculation Worksheet for SD Devices (Continued)