50 NFS2-3030 Programming Manual — P/N 52545:K1 03/20/2012
Program Point Program
PREALARM: Press this softkey to select ALERT or ACTION for the Prealarm function. Refer to
the section on Prealarm in Appendix D, “Intelligent Sensing Applications” for a description of
Alert and Action.
SILENCEABLE: This field determines whether the user can manually
silence a detectors
activated sounder/relay base. Values are as follows:
INTELLIGENT SOUNDER: Press this
softkey to select YES if an Intelligent Sounder Base is
installed for this detector.
SOUNDER BASE SETUP: Press this softkey
to proceed to the Sounder Base Setup screen. This
option will only be available if the INTELLIGENT SOUNDER is set to YES.
CO PRE-ALARM: Press
this softkey to select YES or NO to enable the CO Prealarm function for
the PHOTO/CO smoke detector. This field is only available when programming the PHOTO/CO
smoke detector.
Sounder Base Setup
Figure 3.39 Sounder Base Setup Screen
Soft Keys
AUX TONE 1:Press this softkey to select CONTINUOUS, TEMP-3, TEMP-4, MARCH or
CUSTOM for the first auxiliary tone of the intelligent sounder base.
AUX TONE 1 CONTROL:Press this softkey to enter the Logic, General or Trouble Zone that
will control the activation of the first auxiliary tone of the intelligent sounder base.
AUX TONE 2:Press this softkey to select CONTINUOUS, TEMP-3, TEMP-4, MARCH or
CUSTOM for the second auxiliary tone of the intelligent sounder base.
AUX TONE 2 CONTROL:Press this softkey to enter the Logic, General or Trouble Zone that
will control the activation of the second auxiliary tone of the intelligent sounder base.
NO Not manually silenceable
YES - RESOUND FIRE Silenceable, resound o
n fire alarm events Network and Local Resound
YES - RESOUND SU
PERV Silenceable, resound on supervisory events Network and Local Resound
YES - NO RESOUND Silenceable, does not resound
NOTE: In network applications, specific nodes can be excluded from having the ability to initiate a
resound on the local fire alarm panel. This is programmable via VeriFire Tools. Refer to the VeriFire Tools
help file.
SOUNDER BASE SETUP
L03D123
AUX TONE 1:TEMP-3
AUX TONE 1 CONTROL:ZL0040
AUX TONE 2:TEMP-4
AUX TONE 2 CONTROL:ZLOO41 ACCEPT
VOLUME:HIGH
BACK

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell nfs2-3030 and is the answer not in the manual?

Honeywell nfs2-3030 Specifications

General IconGeneral
BrandHoneywell
Modelnfs2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals