AM_8000  Programming Manual  PAGINA - 51 
AM8000_manu-prog-ENG  Doc. M-160.2-AM-8000-ENG Rev A1  NOTIFIER ITALIA 
 
 DEL 
is the operator which allows to program some activation delays for specific conditions.  
 
The device which has in its CBE equation the “DEL” operator, when its equation is true, waits for the 
programmed time before activating.  
If during this delay time its equation is not true any longer, the timer resets and is ready to start at the next event 
(therefore the output device does not activate) 
 
FORMAT : OF (MM.SS (delay)   MM.SS. (duration - optional) (CONDITION) equation which sets the delay 
start)) 
Where: 
  MM = minutes (2 digits), SS = seconds (2 digits) 
  CONDITION =  it can be an equation of the type: 
 
XGRP (GXXX) 
NOT (Element 1...) 
OR (Element 1...Element 2...) 
AND (Element 1...Element 2..) 
 
  Element = it can be GXXX for a group  (1  400) - LXX S/MXX for an addressable point 
 
Example 1: if the equation of the G90 software group is DEL(00.30   01.30(G21)) then: 
 
 
 
 
 
- After  30 Sec. from the G21 activation  
- the G90 group will activate and will be active  for 1 minute and 30 seconds 
 
 
Example 2: if the equation of the L2M90 output module is DEL (00.30   00.30 (AND (L1S1 L1S4))) 
- After the L1S2 and L1S4 sensors have been in alarm condition for 30 seconds, the  L2M90 module  will be 
active for 30 seconds. 
 
N. B. 
  If a delay is entered = 00.00, then the equation will be active AS SOON AS  the delay start equation 
is  active, and it is active for the time period specified in “duration”.  
 
  Only a DEL operator can exist for each equation  
 
 
  If the  DEL equation duration time is not specified,  the equation will be active until the reset of the 
elements in the equation. 
 
  The maximum value of the duration time is 10 minutes 
  The maximum values of the delay time is 10 minutes. 
     Insert a 
space character