The “SEDEL” operator is equal to the “DEL” operator, with the difference that, if during the delay time the 
equation is not true any longer, the timer continues to count and then it activates the output device. 
To re-set this timer perform an alarm or Fault reset.
 
 
  TIM 
is the operator that allows to program output activations at periodic time intervals. 
 
 There can be two formats  : 
 
 
 
 
FORMAT Type 1 : TIM (SU MO TU WE TR FR SA     00.MM          00.MM) 
     
 
 
 
    
Where : 00 = hours, MM = minutes 
This format allows to perform programmings weekly, for specific days of the week   
 
 
  
 
FORMAT Type 2 :  TIM  (MM   GG   AA           OO.MM       OO.MM) 
 
 
 
 
 
 
Where : MM = month, GG = day, AA =year 
This format allows to perform programmings yearly 
 
 
Example: IF the G90 software group equation is : TIM (SA SU 07.30 13.59) 
THEN the G90 group will be active on Saturday and Sunday from  07.30 a.m.  to 13.59. 
 
 
N.B.: 
 
  If the day, month or year is not specified, the value assumes the meaning of “All days”. 
To not specify anything enter two signs  “  “ refer to the following example: 
 
 TIM (   07.30 13.59) 
  The start  time and end time values, use the 24 hour format (midnight = 00.00 ... 23.59) 
 
 
  The value “00.MM” of end time MUST be higher than the value of the start time.  
 
  The maximum value for start time and end time is 23:59 
 