ID61/62 Series Panel - Operating Manual
Automatic Alarms - What to do
9 997-458-000-8, Issue 8
January 2010
3.3 Fault
Automatic panel actions:
If a fault occurs, the panel automatically does the
following:
a. Operates the internal buzzer (2 sec. on, 1 sec. off).
b. Flashes the appropriate FAULT LEDs, including
numbered ZONE FAULT/ DISABLE/ TEST LED(s) if
appropriate.
c. Operates any control outputs which are associated
in the Control-by-Event Rules with fault events.
Recommended operator actions:
1 A fault message typically displays information as
follows (not all items apply to all types of fault):
a. Fault indication,
b. Fault currently displayed,
c. Total number of faults logged,
d. A text message identifying the nature of the fault,
e. Zone Number,
f. Device Address,
g. Device Type
h. Time fault was logged.
Depending upon the fault message, either:
i If the fault message relates to a specific loop device,
investigate whether the cause of the fault is
immediately apparent and can be corrected.
FAULT 01 / 03 14:55
EARTH FAULT
A
H
BC
D
FAULT 01 / 03 Z01 M12 MCP 14:55
NO REPLY FROM DEVICE >
AHEGFDBC
FAULT 01 / 03 Z01 : M12 MCP 14:55
< - - - Zone Text - - - > < - - - - Device Text - - - - - >
Note: Press the ā
6
ā button to view additional zone text
information. To return to the fault message press
any numeric/cursor key. Alternatively, if no key
is pressed within ten (10) seconds the display
reverts to the fault message.
ii If the fault message relates to a system fault condition,
as displayed below, note the full description of the
fault and notify the authorised servicing company:
Note: e, f, and g are not applicable.
6
1
ZONE FIRE
ZONE FAULT
DISABLE/TEST
FIRE
FAULT
EARTH FAULT
SYSTEM FAULT
SOUNDER: FAULT/DISABLED
FIRE CONTROL O/P: FAULT/DISABLED
2
3
4
DISABLEMENT
TEST
POWER SUPPLY FAULT
PRE-ALARM