ID61/62 Series Panel - Operating Manual
Operator Actions at Panel
37 997-458-000-8, Issue 8
January 2010
4.12 View Mode - User Option
The VIEW MODE User Option allows the user to view
the following system parameters:
a. Log
b. Devices on the loop
c. Faults
d. Input Events
e. Disablements on the loop
f. Maintenance Log*
g. Alarm Count
h. Voltages
i. Version (system and loop software)
* Requires access level 3 passcode.
To display the View Mode menu:
1 From the ‘Status: NORMAL’ message, press the ‘ ’
button. The LCD prompts for a Level 2/3 access code.
Note: If an incorrect access code is entered, the LCD
displays an ‘ERROR - INCORRECT
PASSCODE ! ! !’. After one minute the LCD returns
to the ‘Status: NORMAL’ message.
2 Either turn the keyswitch or, using the numeric keypad,
enter the correct Level 2 access code and confirm
using the ‘
5
’ button. The Level 2 menu is displayed
with the user number ([U0] to [U9]) in the top left-hand
corner.
3 Using the numeric keypad, press the ‘
4
’ button to
select the View Mode menu:
4 Press the ‘
2
/
8
’ buttons to display further menu
options:
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . . < : BackSp
[U0] 1:Test 2:Disable/Enable 3:Clock
4:View Mode 5:Commission 6:Print
[U0 View] 1:Log 2:Devices 3:Faults
4:Input Events 5:Disabled ¦ : More
5
4
82
or
[U0 View] 6: Maint. 7: Alarm Count
8: Voltages 9: Version ¦ : More