100 SFP-5UD & SFP-10UD Series Manual— P/N 52879:C2 1/24/2012
Programming Master Programming Level
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a pro-
grammed amount between 0 and 99, for each unique trouble within a 24 hour period. All call limit
counters reset (clear) at each midnight. Separate limit counters keep track of each unique type of
trouble. Note that the number of phone line (communication) faults called to the Central Station
are not limited by this feature. No subsequent restoral message is sent to the Central Station(s) for
a particular trouble whose call limit has been reached. Local DACT annunciation will still track the
particular trouble and restoral.
Secondary # Zone 6 Dirty FT6 FJ6
Secondary # Zone 7 Dirty FT7 FJ7
Secondary # Zone 8 Dirty FT8 FJ8
Secondary # Zone 9 Dirty FT9 FJ9
Secondary # Zone 10 Dirty FT10 FJ10
Secondary # Earth Fault ET38 ER38
Secondary # Low Battery Fault YT0 YR0
Secondary # No Battery Fault YT0 YR0
Secondary # Telco Primary Line Fault LT1 LR1
Secondary # Telco Secondary Line Fault LT2 LR2
Secondary # NAC #1 Fault ET32 ER32
Secondary # NAC #2 Fault ET33 ER33
Secondary # NAC #3 Fault ET34 ER34
Secondary # NAC #4 Fault ET35 ER35
Secondary # NAC #1 Disable ET101 ER101
Secondary # NAC #2 Disable ET102 ER102
Secondary # NAC #3 Disable ET103 ER103
Secondary # NAC #4 Disable ET104 ER104
Secondary # Charger Fault YP YQ
Secondary # Comm Trouble Primary # YC1 YK1
Secondary # Comm Trouble Secondary # YC2 YK2
Secondary # Printer Fault VT VR
Secondary # ANN-Bus Fault ET61 ER61
Secondary # Option Card Fault ET ER
Secondary # CS CALC Fault YF 000
Secondary # System Off Normal LB LX
Secondary # System Test Message RP 000
Secondary # System Abnormal Test Message RP99 000
Secondary # Power Supply Sync Fault OU OV
Secondary # Upload/Download Request RB 000
Secondary # Upload Successful RS 000
Secondary # Download Successful RS 000
Secondary # Upload/Download Failed RU 000
Secondary # Voice EVAC Fault ET ER
Secondary # Power Supply Sync Fault OU OV
Table 3.7 SIA-DCS Secondary # Event Codes (Continued)
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=CALL LIMIT
Central Station Screen #2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SFP-5UD Series and is the answer not in the manual?

Honeywell NOTIFIER SFP-5UD Series Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SFP-5UD Series
CategoryControl Panel
LanguageEnglish

Related product manuals