What to do if Honeywell Pallet Accuglide ZoneFlex Accumulation Conveyor operational zone control components are not functioning?
- JJames FullerSep 12, 2025
If the operational zone's control components are not functioning, check the following: * Ensure the ZoneFlex™ Module is receiving 24VDC electrical power (LED indicators should be lit). Turn ON the main power source and the 24VDC Power Supply. Secure the Power/Communication Cord/Power Supply connections. Replace the defective ZoneFlex Module if necessary. * Confirm the ZoneFlex Module is receiving sufficient air pressure (25 psi). Turn ON the air source, set the pressure regulator, and secure the air-line connection(s). * Verify the photo-eye (unblocked) and reflector are properly aligned (Red LED indicator should be lit). Adjust the photo-eye mounting bracket.