RAEGuard 3 User Manual
23
5 Default Settings
The following default configurations of RAEGuard 3 transmitter are as follows.
Function
Value/setting
Selectable range
Basic Password /
Advanced Password
1111 / 8888
0000-7999,8000-9999
Fault Current Output
1 mA (±0.5 mA)
1 mA or 2 mA or 3 mA
Inhibit Current Output
2 mA (±0.5 mA)
1 mA or 2 mA or 3 mA
Warning Current Output
3 mA (±0.5 mA)
1 mA or 2 mA or 3 mA
Overrange Current Output
22 mA (±0.5 mA)
21 mA or 22 mA or 23 mA
Sound and Visual Alarm
SP07J
SP07J, SP07A
Location
A0000
A000-Z9999
Language
English
Chinese, English
HART address
0
0-63
RS485 ID, Baud Rate
1,19200
1-247;
4800,9600,38400,57600
Fault Relay**
Energized
Energized, de-energized
Low Alarm Relay*
Energized
Energized, de-energized
High Alarm Relay*
Energized
Energized, de-energized
Low Alarm Latch*
Non-Latching
Latching, non-latching
High Alarm Latch*
Non-Latching
Latching, non-latching
TWA/STEL
Disable
Enable, disable
Calibration interval
90
0-360 (day)
* Alarm relays automatically reset when reading falls within thresholds. If relay configuraed to LATCHING,
then relays must be reset using the Magnetic Wand.
**Fault state (fault relay and analog output<1mA) is always non-latching.
The default configurations for sensor are as follows:
Gas Name
Default
Range
Low Alarm
Low Alarm
Type
High Alarm
High Alarm
Type
O
2
30.0%vol
19.5%vol
Falling
23.5%vol
Rising
H
2
S
100ppm
10ppm
Rising
20ppm
Rising
CO
500ppm
25ppm
Rising
50ppm
Rising
LEL
100%LEL
25%LEL
Rising
50%LEL
Rising
CH
4
-NDIR
100%LEL
25%LEL
Rising
50%LEL
Rising
For details of how to change the configuration of the RAEGuard 3 please refer to
section 12.