RAEGuard 3 User Manual 
81 
 
Appendix A - Modbus
®
 Protocol: 
RAEGuard 3 detectors support RS485 data transmission and communicate 
as MODBUS RTU. The detector provides 4-byte register data. 
Note: The communication only transmits the tested concentration value of 
the gas. 
For example: 34 hex = 52 decimal 
 
RAEGuard  3  detector  supports  RS-485  ModBus  communication  function. 
The  following  are  the  communication  protocols  that  support  this 
communication. 
  Communication settings 
Communication mode: RTU 
Baud rate: 4800,9600,19200,38400,57600 
  Information structure / communication steps 
RAEGuard 3 only supports the 0x03 (read-only register) function code, i.e. 
The detector only supports reading values.   
0x03: Read-only register 
Request information: 
 
Note: The data sent by the detector is 4 bytes long. 
 
For example: 
Request:     01      03  00      08  00      02      45      C9 
Response:     01      03  04      00  00      00      D1      3A      6F     
 
Note: The maximum transmission distance of standard 1.5 mm
2
 
communication cable is less than 1 km.