6.2 System status
RAEGuard 3 provides users with simple and clear system status indications,
which is convenient for users to judge and know the danger level of the site and
whether the instrument is running normally.
System
status
Red LED
Green LED
Yellow
LED
LCD Display
Analog current
output
Low alarm
Solid
Flashing/1s
+Concentration
4-20(±0.1) mA
High alarm
Flashing/1s
Flashing/1s
+Concentration
4-20(±0.1) mA
Low alarm latch
Solid
Flashing/1s
+Concentration
4-20(±0.1) mA
High alarm latch
Flashing/1s
Flashing/1s
+Concentration
4-20(±0.1) mA
Overrange
Flashing/1s
Flashing/1s
22(±0.5) mA
STEL alarm
Solid
Flashing/1s
+Concentration
4-20(±0.1) mA
TWA alarm
Solid
Flashing/1s
+ Concentration
4-20(±0.1) mA
Inhibit
Flashing/1s
Solid
2(±0.5) mA
Warning
Flashing/1s
Flashing/2s
+warning code
3(±0.5) mA
Fault
Flashing/1s
Flashing/1s
+fault code
1(±0.5) mA
Normal
Flashing/1s
4-20(±0.1) mA
Nore: Fault, inhibit and warning current can be set to 1 mA or 2 mA or 3 mA. Overrange current can be set
to 21 mA or 22 mA or 23 mA. But It is not recommended to modify these default values.
For more information on fault codes and warning codes, please refer to Section
11.
6.3 Magnetic Wand
Users can operate RAEGuard 3 via Magnetic Switch.
There are 3-switch , , on the transmitter, which can be recognized by the Magnetic
Switch operating icon on the LCD display.
Left, Mid, Right Click (>1s)
Left, Mid, Right Hold (>3s)
Left, Mid, Right Hold (>20s)