FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 47
Wiring a CMF-300 Module Control Modules
6.3 Wiring a CMF-300 Module
This section contains instructions and diagrams for wiring a Signaling Line Circuit with a
CMF-300 as a Notification Appliance Circuit (NAC).
6.3.1 Wiring a Style Y NAC (Two-Wire) with Addressable Control
Modules
A supervised and power-limited NFPA Style Y (Class B) NAC using a CMF-300 module. Polar-
ized alarm notification appliances are shown connected to the module in a two-wire configuration.
Refer to the Device Compatibility Document for compatible notification appliances and relays.
See “Power Considerations” on page 68 for information on monitoring 24 VDC power.
Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).
24 VDC power must be provided from a UL listed power supply for fire protection use.
A power supervision relay is required only on the last module of the power run.
Do not T-tap or branch a Style Y circuit.
Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt,
P/N SSD A2143-00 (ELR-47K in Canada).
Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.
CMF-300
NAC
24 VDC Nonresettable power
SLC
SLC-nacY.wmf
Note: Module polarities are shown in alarm condition
NOTE: A power
supervision relay is
required only on the
last module of the
power run.
ELR
47K, 1/2-watt
24 VDC Notification
Appliances
Figure 6.2 NFPA Style Y Notification Appliance Circuit