EasyManua.ls Logo

Honeywell SLC - Section 7 Relay Modules; 7.1 Relay Module Description; 7.2 CRF-300 Installation and Wiring

Honeywell SLC
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014 53
Section 7: Relay Modules
7.1 Description
The CRF-300 and the CRF-300-6 modules are addressable modules that provides Form-C relay
contacts.
Ratings for the relay contacts on the module are:
7.2 CRF-300 Installation & Wiring
7.2.1 Setting an SLC address for a CRF-300 Module
Each module is factory preset with an address of “00”. To set an SLC address, refer to “Setting an
SLC address for a Single Point Module” on page 34.
7.2.2 Wiring a CRF-300 Module (Form-C Relay)
The figure below shows a CRF-300 module wired to the Control Panel:
Load Description Application
Maximum
Voltage
Current
Rating
Resistive Non-Coded 30 VDC 3.0 A
Resistive Coded 30 VDC 2.0 A
Resistive Non-Coded 110 VDC 0.9 A
Resistive Non-Coded 125 VAC 0.9 A
Inductive (L/R = 5ms) Coded 30 VDC 0.5 A
Inductive (L/R = 2ms) Coded 30 VDC 1.0 A
Inductive (PF = 0.35) Non-Coded 70.7 VAC 0.7 A
Inductive (PF = 0.35) Non-Coded 125 VAC 0.5 A
NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.
SLC
SLC-frmCtpH.wmf
CRF-300
NO
C
NC
NO
C
NC
Figure 7.1 CRF-300 Wiring Connections