Revision 1.0 SMV800 Modbus User's Guide Page 149
Fluid Type
289
Shows currently selected
fluid Type.This is user
configurable parameter
Note:
Saturated Steam-SP : use
Static Pressure to
calculate the Density for
Saturated steam).
Saturated Steam-PT : use
Process Temperature to
calculate the Density for
Saturated steam)
R/W
uint8
(Byte 0 :-> Bit 0 to 3 )
0 = Gas
1 = Liquid
2 = Steam
3 = Saturated Steam-SP
4 = Saturated Steam-PT
5-15 = Reserved
VCone Y
Method
Shows currently selected
VCone Y Method.This is
user configurable parameter.
(Byte 0 :-> Bit 4 )
0 = Use McCrometer
Method
1 = Use ASME Method
VCone
Simplified
Liquid
Shows currently selected
VCone Simplified Liquid.This
is user configurable
parameter.
(Byte 0 :-> Bit 5 )
0 = Off
1 = ON
Use Wedge
Fixed Flow
Coefficient
Shows currently selected
Use Wedge Fixed Flow
Coefficient.This is user
configurable parameter.
(Byte 0 :-> Bit 6 )
0 = Off
1 = ON
(Byte 0 :-> Bit 7 )
Reserved
Algorithm
Type
290
Shows if the Algorithm is
Advanced Algorithms
type or ASME 1989
Algorithms.
When Algorithm Options is
ON, Algorithm is ASME
1989 Algorithms type. When
OFF, it is Advanced
Algorithms type.
R/W
uint8
0 = Advanced Algorithms
1 = ASME1989 Algorithms

Table of Contents