Page 174 SMV800 Modbus User's Guide Revision 1.0
4.1.1. Differential Pressure sensor calibration
Navigate to Maintenance > Calibration and Correction Records->Differential Pressure
Calibration to perform DP Calibration using SMV Modbus Manager application tool.
The Differential Pressure Calibration screen has following options.
1. DP URV Correct
2. DP LRV Corrrect
3. DP Reset Corrects
4. DP Zero Trim
5. Records that include Current, Last and Previous Calibration/Corrects dates.
By default, Records show the date as Jan 01 1972.
Filter Performace option is provided for process where Noise has to be considered during
calibration.