Page 196 SMV800 Modbus User's Guide Revision 1.0
Warning
Device Warm
Reset
The supply voltage to
the transmitter
terminals has
dropped low enough
to cause a warm
reset of device
Power cycle the
device. If problem
persist, Check the
terminal voltage to be
within limits. If still
problem persists
replace the Terminal
block assembly. If
problem continues
replace the
Communication
module
Bit - 7
118
Display
Communication
Failure
Display
communication
failure
Secure Display
connections and
recheck. If problem
persists, reset the
device. If the problem
still persists, replace
the Display module.
Bit - 8
Display NVM
Corrupt
Communication
module is reporting
corruption of the
Non-Volatile Memory
data (NVM) related to
display screen
configuration.
Power cycle the
device. If the problem
is not seen, verify the
parameters for
configuration changes
made. If the problem
still persists then
NVM might be
damaged so need to
replace Comms
board.
Bit - 9
Communication
Module VCC
Failure
The voltage supply to
the Communication
Module processor is
outside the
operational range of
2.8 to 3.2volts
Power cycle the
device. If problem
persist, Check the
terminal voltage to be
within limits. If
problem continues
replace the Comms
module
Bit - 10
Transmitter
Supply Failure
Power Supply failure
Power cycle the
device. If problem
persist, Check the
terminal voltage to be
within limits. If still
problem persists
replace the Terminal
block assembly. If
problem continues
replace the Comms
module
Bit - 11