EasyManua.ls Logo

Honeywell SMV800 - 2.4 Maintenance

Honeywell SMV800
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision 1.0 SMV800 Modbus User's Guide Page 57
Reynolds Coefficient_r2
Based on the selected Primary element, this is
auto calculated. Applicable when Algorithm
Options = SMV3000 Equation Model = Dynamic
Pipe Diameter Measuring
Temp_TdMeas
Pipe diameter measuring Temperature
Enter the value in the unit selected in the Unit
Configuration screen. For SMV3000 algorithms,
this value is fixed at 68degF. For SMV800
Algorithms, user entered Reference
Temperature will be used to calculate the
adjusted Diameter. Note: that other parameters
like Pipe Thermal Expansion Coefficient,
measured Pipe Diameter and Flowing
Temperature values are also used in the
equation)
Bore Diameter Measuring
Temp_TdMeas
Bore diameter measuring Temperature
Enter the value in the unit selected in the Unit
Configuration screen. For SMV3000 algorithms,
this value is fixed at 68degF. For SMV800
Algorithms, user entered Reference
Temperature will be used to calculate the
adjusted Diameter. Note that other parameters
like Bote Thermal Expansion Coefficient,
measured Bore
Diameter and Flowing Temperature values are
also used in the equation)
Atmospheric Pressure
PSIA
Local Atmospheric pressure in units as per Units
configuration screen
Flow Coefficient
Flow Coefficient used when Algorithm options is
Advanced Algorithms, and Primary Element is
any of the types: Averaging Pitot Tube, Wedge
or Integral Orifice

Table of Contents

Other manuals for Honeywell SMV800

Related product manuals