TR50 - User Guide 41
4.5.6 Configure TR50 Modbus Device via Niagara
Follow the below steps to configure the TR50 Modbus device in Niagara:
Step 1. Add a ModbusAsyncNetwork.
Step 2. Navigate to Config > Drivers > ModbusAsyncNetwork, double-click the
HonModbusDeviceConfig, and open the AX Property Sheet view.
Step 3. Set the Number of Devs to 5, Ping Address to Decimal and 112, and click
Save.
Step 4. Open the AX Property Sheet view of ModbusAsyncNetwork and set the
Port Name and Baud Rate according to the connected Modbus Smart
Sensor.
Step 5. Set the Parity to Even and click Save.