FAASTFLEX FAAST FLEX Product Guide
www.xtralis.com 39
Log example and interpretation
The log header is an important part of the log file as it gives general details about the detector model,
manufacturing date, configuration mode and relay status, below is the list of sections in the log header:
l INFO: this section gives general details about the model, the firmware version serial number, etc.
l Manufacturing date GMT:this section shows the manufacturing date in the GMTtimezone.
l SETTINGS: this section shows details about the configuration mode, alarm and action levels, GPI state,
aspiartor speed, etc.
l STATE: this section records the instantaneous status of the detector.
HEADER reading for salient data: document downloaded from device in date Aug. 24 2022, is a single
channel manufactured in date April, 25 2022 following EN54-20 standard, DIP switches configuration is
0111111110, reference flow 24 l/min, GPI unbalanced.
Figure6-6: Sample Event Log
LOG Desc
Row 1) device power ON
Row 2) Alarm CH1 smoke level passed from 50 to 200,
Row 3) Exit from alarm CH1
Row 4) Front cover opened by operator
Row 5) Log requested -pushed button enter-
Row 6) Log downloaded on USB stick.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Xtralis FAAST FLEX FLX-020 and is the answer not in the manual?

Honeywell Xtralis FAAST FLEX FLX-020 Specifications

General IconGeneral
BrandHoneywell
ModelXtralis FAAST FLEX FLX-020
CategorySmoke Alarm
LanguageEnglish

Related product manuals