Removing and replacing a fanRemoving and replacing a fan
ProcedureProcedure
1. If physically powering down a server with the front bezel installed, remove the front bezel .
2. Power down the server.
3. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
4. Disconnect all peripheral cables from the server.
5. Remove the server from the rack .
6. Place the server on a flat, level work surface.
7. Remove the access panel .
8. If installed, remove the processor air baffle before removing fan from bay 1 or 2.
9. Remove the fan.