Specifications 101
Rated input current
9.2 A at 100 VAC
9.5 A at 110 to 120 VAC
6.6 A at 200 to 240 VAC
Maximum rated input power
1000 W at 120 VAC input
1320 W at 230 VAC input
BTUs per hour
3408 at 120 VAC input
4500 at 230 VAC input
Power supply output
Power supply output
800 W at 100 VAC input (low
line)
900 W at 108 V to 132 VAC
input (low line)
1200 W at 200 V to 240 VAC
input (high line)
Rated steady-state power
800 W at 100 VAC input
900 W at 120 VAC input
1200 W at 200 V to 240 VAC
input
Maximum peak power
800 W at 100 VAC input
900 W at 120 VAC input
1200 W at 200 V to 240 VAC
input
HPE 1500 W Common Slot -48 VDC Hot-plug Power Supply
Specification Value
Input requirements
Rated input current
42.0 A at -40 VDC input
33.5 A at -48 VDC input
22.2 A at -72 VDC input
Rated input power (W)
1621 W at -40 VDC input
1607 W at -48 VDC input,
nominal input
1598 W at -72 VDC input
Rated input power (BTUs per
hour)
5530 at -40 VDC input
5484 at -48 VDC input
5451 at -72 VDC input
Power supply output
Rated steady-state power (W)
1500 W at -40 VDC to -72 VDC
1500 W at -40 VDC to -72 VDC
CAUTION:
This equipment is designed to permit the connection of the earthed conductor of
the DC supply circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
• This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC