Specifications 102
supply system earthing electrode conductor is connected.
• This equipment must be located in the same immediate area (such as adjacent cabinets) as
any other equipment that has a connection between the earthed conductor of the same DC
supply circuit and the earthing conductor, and also the point of earthing of the DC system.
The DC system must be earthed elsewhere.
• The DC supply source is to be located within the same premises as the equipment.
• Switching or disconnecting devices must not be in the earthed circuit conductor between
the DC source and the point of connection of the earthing electrode conductor.
CAUTION: To reduce the risk of electric shock or energy hazards:
•
This equipment must be installed by trained service personnel, as defined by the NEC and
IEC 60950-1, Second Edition, the standard for Safety of Information Technology
Equipment.
• Connect the equipment to a reliably grounded SELV source. An SELV source is a
secondary circuit that is designed so normal and single fault conditions do not cause the
voltages to exceed a safe level (60 V DC).
• The branch circuit overcurrent protection must be rated 24 A.
HPE 1500 W Common Slot Platinum Plus Hot-Plug Power
Supply (94% efficiency)
Input requirements
Rated input frequency
Maximum rated input power
Power supply output
Rated steady-state power
1500 W at 200 V to 240 VAC
input
Maximum peak power
1500 W at 200 V to 240 VAC
input