Bay 1 Bay 2 Bay 3 Bay 4 Bay 5 Bay 6 Redundant
hot-plug
support
— — — — Fan Fan No
Blank Fan Fan Fan Fan Fan No
Fan Fan Fan Fan Fan Fan Yes
Fan mode behavior
• In non-redundant fan mode, a fan failure or a missing fan causes:
◦ The system Health LED to flash amber.
◦ The operating system to orderly shut down.
• In redundant fan mode:
◦ A fan failure or a missing fan will switch the system to non-redundant fan mode.
This change is indicated by the Health LED flashing amber. The system continues to operate normally
in this mode.
◦ A second fan failure or a missing fan causes the operating system to orderly shut down.
Fan speed
The server supports variable fan speeds. The fans operate at minimum speed until a temperature change
requires a fan speed increase to cool the server. The server shuts down during the following
temperature‑related scenarios:
• At POST and in the OS, iLO 5 performs an orderly shutdown if a cautionary temperature level is detected.
If the server hardware detects a critical temperature level before an orderly shutdown occurs, the server
performs an immediate shutdown.
• When the Thermal Shutdown feature is disabled in the BIOS/Platform Configuration (RBSU), iLO 5 does
not perform an orderly shutdown when a cautionary temperature level is detected. Disabling this feature
does not disable the server hardware from performing an immediate shutdown when a critical temperature
level is detected.
CAUTION:
A thermal event can damage server components when the Thermal Shutdown feature is disabled in
the BIOS/Platform Configuration (RBSU).
Installing the fan cage
Prerequisites
Before you perform this procedure, make sure that you have the following items available:
• Fan cage option kit
• T-15 Torx screwdriver
Procedure
1. Remove the front bezel on page 39.
2. Power down the server on page 38.
3. Remove all power:
108 Fan mode behavior