Shenzhen Hpmont Technology Co., Ltd Appendix A Parameters
HD20 Series Inverters User Manual -135-
No. Name Range
Factory
Default
Unit
Modified
attributes
Setting
when motor 2 is forward
F13.47
Motor torque limitation
when motor 2 is reverse
0.0-200.0% (F13.03) 180.0% 0.1% ×
F13.48
Recreated torque
limitation when motor 2 is
forward
0.0-200.0% (F13.03) 180.0% 0.1% ×
F13.49
Recreated torque
limitation when motor 2 is
reverse
0.0-200.0% (F13.03) 180.0% 0.1% ×
F13.50 Reserved
F13.51 Reserved
F13.52 Reserved
Group F14 Reserved
Group F15 Digital I/O Terminal Parameters (refer to pages 77
88)
F15.00
DI1 terminal function
selection
0: Reserved
1: Inverter enabled
2: FWD function
3: REV function
4: Three-wire operation mode
5,6,7: Frequency source
selection 1, 2, 3
8: AI to be the frequency
source
9,10: Run command source
selection 1,2
11: Terminal control mode to
be the run command source
12: External stop command
input
13-16: Mult i-step frequency
terminal 1-4
17: Frequency ramp (UP)
18: Frequency ramp (DN)
19: Clearing auxiliary
frequency setting
20,21: Forward and reverse
jog 1 command control input
(JOGF1/ JOGR1)
22,23: Forward and reverse
jog 2 command control input
(JOGF2/ JOGR2)
24: Jog 1 command control
input
25: Jog 1 direction control
input (Remark: When select 20
and 21, the functions 24 and
25 are invalid)
0 1 ×
F15.01
DI2 terminal function
selection
0 1 ×
F15.02
DI3 terminal function
selection
0 1 ×
A