PVCHECKs-PRO
EN - 25
7. Press and hold the GO/STOP key for at least 3s in
order to start the test. In case no error conditions occur,
the instrument displays the message “Measuring…” as
shown in the screen to the side. In field “Vtest”, the real
test voltage generated by the instrument is shown. Test
duration may vary according to the presence of stray
capacitances
M 15/10 – 18:04
(+) (-)
Vtest - - - - - - V
Riso - - - - - - M
Rp - - - M
VPN VPE VNE
1480V 750V -748V
Measuring…
DUAL 1500V 1.00M
MODE Vtest. Lim.
8. The instrument carries out the following measurements in
a sequence:
Insulation between positive pole (+) of the string and
earth connection
Insulation between negative pole (-) of the string and
earth connection
Calculation of the value of resistance Rp given by the
parallel of measurements (+) and (-)
If “RpLim”, the instrument shows the message “OK”, to
indicate a positive result of measurement.
Press the SAVE key to store the test result in the
instrument’s memory (see § 7.1) or the ESC/MENU key
to exit the screen without saving and go back to the main
measuring screen.
M 15/10 – 18:04
(+) (-)
Vtest 1510 1515 V
Riso >100 >100 M
Rp >100 M
VPN VPE VNE
1480V 750V -730V
OK
DUAL 1500V 1.00M
MODE Vtest. Lim.
6.4.2. Measuring insulation – TMR mode
1. Position the cursor onto M by using the arrow keys
(,) and confirm with ENTER. The display shows the
screen to the side. By using the arrow keys (,) again,
select the “TMR” measuring mode, in position “MODE”.
M 15/10 – 18:04
Vtest(-) - - - V
Ri(-) - - - M
Time - - - s
DAR - - - PI - - -
VPN VPE VNE
0V 0V 0V
TMR 1500V 1.00M 3s
MODE Vtest. Lim. Time
2. Use the arrow keys or and select the position
Vtest” to set the test voltage.
3. Use the arrow keys (,) to select one of the following
test voltages (Vnom): 250, 500, 1000, 1500VDC. Please
remember that, in compliance with standard IEC/EN
62446-1, test voltage Vtest must be rated voltage of the
installation.
M 15/10 – 18:04
Vtest(-) - - - V
Ri(-) - - - M
Time - - - s
DAR - - - PI - - -
VPN VPE VNE
0V 0V 0V
TMR 1500V 1.00M 3s
MODE Vtest. Lim. Time