PVCHECKs-PRO
EN - 51
9. Once Voc and Isc measurements are completed, the
message “Waiting for irradiance values” is shown in
case a remote unit SOLAR03 is recording but not
connected to the instrument. Wait for the remote unit to
download the data to display the measurement results
@STC
IVCK 15/10 – 18:04
Voc@STC - - - V
Isc@STC - - - A
Voc Nom 1485 V
Isc Nom 11.25 A
Rp >100 M OK
R+ >100 R- >100 M
RPE 1.1 OK
Waiting for irradiance values
1500V 1.00M 2 0.2
VTest ISO RPE
><
10. In case the remote unit SOLAR03 has been activated
and connected, but the irradiance value is not valid, the
message to the side is shown on the display. Check the
status of the remote unit
IVCK 15/10 – 18:04
Front
Irr. - - - W/m2
Temp. - - - °C
SOLAR03 23051203
Module: SUNPOWER318WTH
VPN VPE VNE
1480V 740V -740V
Check inputs of Rem.Unit
1000V 1.00M 2 0.25
VTest ISO RPE
><
11. In case measurements are carried out without remote
unit (see § 6.7.2), but the instrument has previously been
paired to a remote unit, the message to the side appears
on the display. Enter the remote unit’s configuration
menu (see § 6.2) and select “Unpair” to unpair the
remote unit.
IVCK 15/10 – 18:04
Front
Irr. - - - W/m2
Temp. - - - °C
SOLAR03 23051203
Module: SUNPOWER318WTH
VPN VPE VNE
1480V 740V -740V
Rem.Unit not connected
1000V 1.00M 2 0.25
VTest ISO RPE
><