Figure 6-13 Signal cable ports
Table 6-3 COM port denition
No. Label Denition Description
1 PE Shield layer grounding Shield layer grounding
2 Enable- Enable signal GND Connects to the enable signal
GND of the inverter.
3 Enable+ Enable signal+ Connects to the positive
enable signal of the inverter.
4 485A RS485A, RS485
dierential signal+
Connects to the RS485 signal
port + of the inverter or
cascaded battery.
5
6 485B RS485B, RS485
dierential signal–
Connects to the RS485 signal
port - of the inverter or
cascaded battery.
7
8 CANL Extended CAN bus port Used for signal cable
cascading in battery
cascading scenarios.
9 CANH Extended CAN bus port Used for signal cable
cascading in battery
cascading scenarios.
10 PE Shield layer grounding Shield layer grounding
Terminals
NO TE
Identify the signal terminal pins according to the following gures, and connect cables
according to Table 6-3. When you insert the communications terminal of the power
control module, the silk screens on the two sides of the communications port are
dierent. Insert the communications terminal according to the following gures.
The communications terminals on the inverter side need to be connected to RS485+
\RS485-, EN+\EN-, and PE.
LUNA2000-(5-30)-S0
User Manual 6 Electrical Connection
Issue 15 (2024-01-12) Copyright © Huawei Digital Power Technologies Co., Ltd. 91