Huawei MTS9300A - 2 Product Overview; 2.1 Overview

Huawei MTS9300A
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cable Type Maximum
Current (A)
Minimum Cross-
Sectional Area (mm
2
)
Maximum Cross-
Sectional Area (mm
2
)
- 63 10 16
- 32 4 16
- 16 1.5 16
Battery cable 200 25 x 2 35 x 2
NOTE
The size data in the table is applicable when the ambient temperature is 30°C (in air) and only cables in a
single loop are involved.
When the ambient temperature is not 30°C or cables in multiple loops are routed together, use cables with
larger cross-sectional areas if the cabling distance is long.
Battery cables should be able to withstand a temperature of at least 105°C.
2.2 Tools
NO TICE
Use insulated tools. The following gure is for reference only.
Table 2-2 Tools
MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide 2 Installation Preparations
Issue 01 (2021-05-30) Copyright © Huawei Technologies Co., Ltd. 16