Setting Description
Peak Shaving
Para
Rated Phase Volt Set the parameter based on the
rated voltage of the power grid.
Default value: 220 V.
Peak Shaving SOC If power failure occurs, reserve
the battery capacity for peak
shaving.
Peak Shaving SOC
(Mix.)
Power-On
Hysteresis for
LLVD in Peak
Shaving
By default, this parameter does
not need to be set.
Batt Backup
Enable
Indicates whether the peak
shaving battery is used as the
backup battery in the case of
power failure. Default value: No.
Allow A/C
Shutdown in Peak
Shaving
Indicates whether the air
conditioner can be turned o
during peak shaving. You are
advised to disable this function.
Allow LLVD n
Disconnection in
Peak Shaving
Indicates whether to power o
the minor loads when the battery
capacity reserved for peak
shaving is fully discharged.
8.9 Setting Sensor Parameters
Set sensor parameters based on site requirements.
Table 8-7 Setting sensor parameters
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Settings
Parameters
Settings
Setup Parameter Sensor Cong Door Sensor Yes, No
NOTE
Set these parameters to
Yes or No as required.
Water Sensor
Smoke Sensor
Batt. Temp.
Sensor
Temp1 Sensor
MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide 8 Commissioning