Table 4-1 DIP switch settings
Toggle
Switch 1
Toggle
Switch 2
Toggle
Switch 3
Toggle
Switch 4
Toggle
Switch 5
Toggle
Switch 6
Address of Digital
Temperature and
Humidity Sensor
ON ON OFF OFF ON ON 51
----End
4.3.2 (Optional) Installing a Smoke Sensor
Procedure
Step 1 Remove the screws that secure the smoke sensor to the top left of the cabinet.
Step 2 Secure the smoke sensor base to the top of the cabinet by using the removed
screws.
Ensure that the switch on the smoke sensor base faces the cabinet door.
Step 3 Secure the smoke sensor to the base.
Figure 4-6 Installing a smoke sensor
Step 4 Connect one end of the communications cable to the smoke sensor and the other
end to the SMOKE port on the UIM panel.
MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide 4 Installing Components
Issue 01 (2021-05-30) Copyright © Huawei Technologies Co., Ltd. 27