LLVD n Mode Voltage Mode/ Time
Mode
LLVD n Voltage 36.0-56.0 V
LLVD n Recon Volt 37.0-58.0 V
LLVD n Time 0–6000 min
LLVD Delay Time 5-90s
8.8 Setting AC Peak Clipping Parameters
Set peak shaving parameters based on site requirements.
Table 8-6 Setting peak shaving parameters
Main
Menu
Second-
Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Setting Description
Parameters
Settings
AC Peak
Shaving
AC
parameters
Mains Peak Shave
Enb
Enable or disable the peaking
shaving function. When the
mains capacity or circuit breaker
capacity is insucient, you are
advised to enable the peak
shaving function.
Cap for Peak
Shave
If the input transformer power
is insucient, set this
parameter to the transformer
power (unit: kW).
If the input transformer power
is
sucient, keep the default
value.
Breaker Rated
Curr
If the circuit breaker capacity
is insucient, set this
parameter to the circuit
breaker capacity (unit: A).
If the circuit breaker capacity
is
sucient, keep the default
value.
Derating Coef Indicates the high temperature
derating coecient of the circuit
breaker. Keep the default value
(0.8) unless otherwise specied.
MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide 8 Commissioning
Issue 01 (2021-05-30) Copyright © Huawei Technologies Co., Ltd. 56