Loading...
Item Setting Value
Battery model
NOTE
If the battery model is set to ESM-A, you do not need to set battery
parameters after the SMU restarts.
The SMU may
restart.
Yes
Battery n
Connected
Yes/No
NOTE
If battery routes 1 and 2 are respectively connected to a battery
string (a battery string consists of four 12 V, 150 Ah batteries in
series), set Battery 1 Connected and Battery 2 Connected to Yes
and others to No, and set Single-String Cap. to 150 Ah.
If battery route 1 is connected to two parallel battery strings (one
battery string consists of four 12 V, 150 Ah batteries in series), set
Battery 1 Connected to Yes and others to No, and set Single-
String Cap. to 300 Ah.
Single-String
Cap.
Rated capacity of each battery string
NOTE
A battery string includes a set of batteries controlled by one circuit
breaker or fuse.
The SMU may
restart.
Yes
8.4 Setting the Date and Time
NO TE
The LCD backlight turns o if no button is pressed within 30 seconds.
Re-login is required if no button is pressed within 1 minute.
The preset password for login is 000001.
Set the date and time as required. Skip the setting if they have been correctly set
in the setup wizard.
Table 8-2 Setting the date and time
Main Menu
Second-Level
Menu
Third-Level
Menu
Default Value Settings
Setting Wizard Date and Time
NOTE
The date and time
vary with time
zones. Set the
time zone, date,
and time based
on the local
situation.
Time Zone UTC +08:00
Beijing
Set to the local time
zone.
Date and Time - Set to the local date
and time.
MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide 8 Commissioning
Issue 01 (2021-05-30) Copyright © Huawei Technologies Co., Ltd. 54