EasyManua.ls Logo

Huawei MTS9300A - 3.6.3 Temperature Sensor; 3.7 Light

Huawei MTS9300A
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 5-8 Installing DC output power cables
(1) DC load
----End
Connecting DC Output Power Cables to 63 A Circuit Breakers
Step 1 Use cables (cross-sectional area: 1.5–16 mm
2
) and cord end terminals to prepare
DC output power cables.
Table 5-2 Preparing cables
Cross-Sectional
Area
Recommended Cord End Terminal
Specications
Recommended Bare Wire
Specications
1.5 mm
2
Pre-insulated and with an insertion
depth of 18 mm
16 mm
2
NOTICE
Cord end terminals are
recommended. When bare wires are
used, you are advised to add heat
shrink tubing to ensure that the wire
ends are not split.
4 mm
2
Pre-insulated and with an insertion
depth of 18 mm
10 mm
2
Pre-insulated and with an insertion
depth of 18 mm
16 mm
2
Pre-insulated and with an insertion
depth of 18 mm (supports bare wire
installation)
MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide 5 Installing Cables
Issue 01 (2021-05-30) Copyright © Huawei Technologies Co., Ltd. 35

Table of Contents

Other manuals for Huawei MTS9300A

Related product manuals