A Alarm List
The battery voltage reaches
the EOD threshold due to
continuous discharge.
Check the status of the
battery cabinet and turn on
the BCB switch.
Check the mains, and
charge batteries in a timely
manner.
The cell temperature is too
high.
Take measures to reduce the
ambient temperature.
The cell temperature is too
low.
Take measures to increase the
ambient temperature.
The battery voltage
reaches the high-voltage
alarm threshold.
The cell temperature is too
high.
Check the UPS status.
Check the lithium battery
cabinet status.
The battery voltage
reaches the low-voltage
alarm threshold.
The cell temperature is too
low.
The input fuse is blown.
Check whether the input
fuse is normal.
Check the mains, and
charge batteries in a timely
manner.
Restore the mains input to
the UPS and start the
charger to charge the
battery.
The battery charge current
reaches the overcurrent
alarm threshold.
The battery discharge
current reaches the
overcurrent alarm
threshold.
Check the UPS charger
status.
Check the lithium battery
cabinet status.
Check whether the UPS is
overloaded. Reduce the UPS